STUDI EVALUASI JARINGAN DISTRIBUSI AIR BERSIH PDAM DI KECAMATAN PANDAAN KABUPATEN PASURUAN MENGGUNAKAN EPANET 2.0
Abstract
ABSTRAK
Penyediaan air bersih di Kecamatan Pandaan difasilitasi oleh PDAM Kabupaten Pasuruan. Bertambahnya jumlah pelanggan PDAM setiap tahun kebutuhan air bersih meningkat. Sistem jaringan distribusi diharapkan dapat memenuhi kriteria hidrolis. Mengantisipasi meningkatnya jumlah pelanggan diperlukan suatu evaluasi mengenai kebutuhan air bersih di masa mendatang serta jaringan distribusi air bersih PDAM yang dapat memenuhi kriteria hidrolis menggunakan software Epanet 2.0 dalam analisis hidrolisnya. Tujuan dari penelitian ini yaitu mengetahui kebutuhan air bersih PDAM yang harus dipenuhi serta mendukung peningkatan pelayanan PDAM sehingga pelanggan mendapatkan air bersih yang optimal. Metode yang digunakan dalam perhitungan proyeksi pelanggan yaitu metode geometri, aritmatik dan eksponensial. Hasil dari penelitian ini menunjukkan jumlah proyeksi pelanggan PDAM pada tahun 2032 sebesar 14.920 jiwa. Pada tahun 2032 kebutuhan air rata-rata sebesar 19,643 liter/detik, kebutuhan air harian maksimum sebesar 23,572 liter/detik dan kebutuhan air pada jam puncak sebesar 36,831 liter/detik. Hasil perbandingan jumlah kebutuhan air dengan debit produksi sumber air tidak mampu mencukupi kebutuhan air pada saat jam puncak maka alternatif yang diberikan yaitu menambah reservoir baru. Dari hasil simulasi jaringan eksisiting menggunakan software Epanet 2.0 tidak memenuhi kriteria hidrolis. Pada simulasi jaringan kondisi pengembangan tahun 2032 yang telah dilakukan penyesuaian dimensi pipa menjadi 8â€, 6â€, 4â€, 3â€, 2 †dan 2†terlihat bahwa jaringan sudah memenuhi kriteria hidrolis. Pressure terkecil terdapat pada node 19 sebesar 6,81 m, sedangkan pressure tertinggi terdapat pada node 71 sebesar 78,07 m. Velocity terkecil terdapat pada pipa 82 dan 83 sebesar 0,30 meter/detik, sedangkan velocity terbesar terdapat pada pipa 42 sebesar 3,44 meter/detik.
Kata Kunci: Epanet 2.0, Jaringan Distribusi Air Bersih, Kebutuhan Air Bersih
ABSTRACT
              The provision of clean water in Pandaan District is facilitated by PDAM Pasuruan Regency. With the increasing number of PDAM customers, the need for clean water increases every year. The distribution network system is expected to meet the hydraulic criteria. Anticipating the increasing number of customers requires an evaluation of future clean water needs as well as PDAM clean water distribution networks that can meet the hydraulic criteria using EPANET 2.0 software in their hydraulic analysis. The purpose of this study is to determine the PDAM's clean water needs that must be met and to support the improvement of PDAM services so that customers get optimal clean water. The methods used in calculating customer projections are geometric, arithmetic and exponential methods. The results of this study show that the projected number of PDAM customers in 2032 is 14.920 people. In 2032 the average water demand is 19,643 liters/second, the maximum daily water demand is 23,572 liters/second and the water demand during peak hours is 36,831 liters/second. The results of the comparison of the amount of water demand with the production discharge of water sources are unable to meet the water demand during peak hours, so the alternative given is to add a new reservoir. From the simulation results of the existing network using Epanet 2.0 software does not meet the hydraulic criteria. In the network simulation for development conditions in 2032, which has adjusted the pipe dimensions to 8â€, 6â€, 4â€, 3â€, 2 1/2†and 2†it can be seen that the network meets the hydraulic criteria. The smallest pressure is at node 19 of 6,81 m, while the highest pressure is at node 71 of 78,07 m. The smallest velocity is in pipes 82 and 83 of 0,30 meters/second, while the largest velocity is in pipe 42 of 3,44 meters/second.
Keywords: Epanet 2.0, Clean Water Distribution Network, Clean Water Needs
ÂFull Text:
PDF (Bahasa Indonesia)References
Badan Standarisasi Nasional. (2011). Tata Cara Perencanaan Teknik Jaringan Distribusi dan Unit Pelayanan Sistem Penyediaan Air Minum. SNI 7509:2011.
Kencanawati, M., Mustakim, H., & Ramdhan, M. (2016). Analisis Sistem Distribusi Air Bersih Berdasarkan Parameter Debit Dan Tekanan Air (Studi Kasus Perumahan Nusantara Lestari Km.8 Balikpapan). Jurnal TRANSUKMA , 2(1), 1–6.
Noerhayati, Eko, Anita Rahmawati, And Satriyo Yoga Wahyudi. 2020. “Water Spread Test On Iot (Internet Of Things) Based Automatic Irrigation System.†Journal Innovation Of Civil Engineering (JICE) 1 (1): 1. Https://Doi.Org/10.33474/Jice.V1i1.9057.
Peraturan Pemerintah. 2007. No 18, Tentang Penyelenggaraan Pengembangan Sistem Penyediaan Air Minum.
Pribadi, G., Noerhayati, E., & Rachmawati, A. (2019). Perencanaan Sistem Jaringan Air Bersih pada Perumahan The Araya Cluster Jasmine Valley Kota Malang. Jurnal Rekayasa Sipi (e-journal), 6(1), 116-121.